(可程式恒溫恒濕箱TEMI880控制器安裝說明書)
區(qū)分詳細(xì)內(nèi)容規(guī)格畫面LCD5.7英寸彩色觸摸屏程序組/段120組/1200段反復(fù)/附加功能全部反復(fù):zui多999次(可無限反復(fù)),部分反復(fù):zui多99次/圖像鏈接和編輯PID控制PID組溫度,濕度組:6個區(qū),溫度組:3個區(qū)輸入傳感器和測定范圍輸入(指示精度)傳感器種類測定范圍溫度(±0.1%ofFS)Pt1100ΩPt2100ΩDCV-50.00~150.00℃-100.0~200.0℃-1.000~2.000V(-100.0~200.0℃)濕度(±1%ofFS)Pt1100ΩDCV-10.0~110.0℃(0.0~100.0%RH)1.000~5.000V(0.0~100.0%RH)4~20mA輸出控制輸出2點(diǎn)(溫度,濕度)輸出規(guī)格電壓輸出(SSR)電壓:15VDC以上,zui小Pulse寬度:5ms電流輸出(SCR)電流輸出(SCR):4~20mADC,負(fù)荷阻抗:zui大600Ω傳送傳送輸出2點(diǎn)(溫度,濕度),輸出形式:PV,SP,MV輸出信號/負(fù)荷阻抗4~20mADC/zui大600Ω接點(diǎn)輸入輸入種類DI1:RUN/STOP固定,DI2~DI8:可更改各個錯誤信息名稱接點(diǎn)用量zui大12VDC,10mA接點(diǎn)輸出接點(diǎn)規(guī)格zui多20點(diǎn)(基本:10點(diǎn),選項:10點(diǎn))接點(diǎn)用量NormalOpen(zui大30VDC/,250VAC/),NormalClose(zui大30VDC/1A,250VAC/2A)輸出種類(Total33點(diǎn))InnerSignal:8點(diǎn),TimeSignal:4點(diǎn),AlarmSignal:4點(diǎn),On/OffSignal:4點(diǎn),溫度,濕度RunSignal:2點(diǎn),溫度,濕度Up/Soak/DownSignal:6點(diǎn),DrainSignal:1點(diǎn),ErrorSignal:1點(diǎn),PTEndSignal:1點(diǎn),1stRefSignal:1點(diǎn),2ndRefSignal:1點(diǎn)電源電源額定電壓:100~240VAC(±10%),50/60Hz,消費(fèi)電力:zui大20W絕綠阻抗500VDC20MΩ鋰電池設(shè)定數(shù)據(jù)保存用(zui少10年)內(nèi)電壓每分鐘2000VAC通訊協(xié)議PC-Link,MODBUS(ascii,RTU)通訊種類RS232C/RS485-通訊距離zui長1.2Km,zui多連接99臺,通訊速度:zui快達(dá)9600bps資料備份存儲媒介UDC300(選項):可使用凡用USB內(nèi)存條存儲功能備份修復(fù)程序信息與設(shè)定值,儲存溫度,濕度指示值